Plastic Insulated and Sheathed Branch Cable with the Rated voltage at 0.6/1kV and Below
Current Location : HomePage > Products
Plastic Insulated and Sheathed Branch Cable with the Rated voltage at 0.6/1kV and Below

  Executive Standard
  This product is manufactured in line with the general industry standard entitled Q/AXHTD07-2000 which refers to the JGS. 


  Usage
  It is suitable to be used for the copper-cored or copper alloy-cored plastic insulating and sheathed branch cable for power, electrical and lighting device whose AC rated voltage is 0.6/1kV in residential areas, high-rise office buildings, tunnels and factories, which is quite easy to install.

  Model and Name

Model Name
FZYJV-0.6/1kV

Rated voltage 0.6/1kV XLPE insulated PVC sheathed branch cable

FZVV-0.6/1kV

Rated voltage 0.6/1kV branch PVC insulated copper cable


  Description of Each Code in Model


Item Code Description
Series FZ Branch cable
Insulation V Polyvinyl chloride PVC
YJ
Sheath V XLPE
Specifications cores × cross-section Core number × areamm2 PVC

  Examples
  This product is mainly described by model, specification, numbers of core, nominal cross-sectional area of the main line, nominal cross-sectional area of the branch cable, insulating effectiveness, color and the standard number. For instance:
  FZVV-O. 6/1kV 1 × 185 (95) or Q/XH11 or QIAXHT007-2000 can be made use of to represent the single-core, copper-cored polyoxyethylene insulating Yun poly ethylene sheathed branch cable with the main line’s cross-sectional area at 185mm2 and the branch line’s cross-sectional area at 95mm2.

  Characteristic Features
  ① Rated voltage (Uo /U): 0.6/1kV.
  ② The highest long-term allowable working temperature for the cable’s conductor:
It is 70℃ for the PVC insulated cables while 90℃ for the XLPE insulated ones.
  ③ The ambient temperature should not be less than 0 ℃ while laying the cable. When it is below 0℃, it should be pre-heated in advance.
  ④ The recommended bending radius of the cable should be no less than 12 times of its outer diameter.
  ⑤ The conductor’s DC resistance of the cable is shown in Table 3 while the insulation resistance is supposed to be no less than 200MΩ.
  ⑥ The molded branch section of the branch cable should be able to withstand the heat cycle test for 250 times.
  ⑦ The branch cable is supposed to be able to withstand the 3.5kV/5min AC voltage test.

Nominal sectional Area of conductor mm2

Conductor's DC resistance at 20 ℃ ≤ Ω /km Conductor's cross-sectional area mm2 Conductor's resistance at 20 ℃ ≤ Ω /km Nominal cross-sectional Area of conductor mm2 Conductor's DC resistance at 20 ℃ ≤ Ω /km
6 3.08 50 0.387 185 0.0991
10 1.83 70 0.268 240 0.0754
16 1.15 95 0.193 300 0.0601
25 0.727 120 0.153 400 0.0470
35 0.524 150 0.124 500 0.0366